Back to Assets

001

06 - Fire Detection Systems - Panels

ROHR PTY LTD
Compliant
Type
06 - Fire Detection Systems - Panels
Tier
ASSET
Location
Back of Main Shed
Barcode
—
Make
Notifier
Model
2800
Size
1 Loop
Quantity
—
Expected life (yrs)
—
Installed
—
Base date
—
Last inspected
16 May 2025
Inspection ref
—
Serviced by
Scott Osborne
Signed off
—
Active
Yes
Inspection order
0

Internal note

Battery Capacity Test Results 22/9/2023 Q = 0.62 Amp A = 4.32 Amp Required = 24.0 A/H Fitted = 2 x 12 volt 35 A/H Last Replaced = 22/06/2022 Result = PASS